CFKTT - LEAD-ACID BATTERY,NP 1.2-12

  • MSDS: CFKTT
  • Manufacturer: YUASA EXIDE INC
  • Product Name: LEAD-ACID BATTERY,NP 1.2-12
  • National Stock Number: 6140-01-371-0520
Product Identification

Product ID:LEAD-ACID BATTERY,NP 1.2-12
MSDS Date:06/01/1996
FSC:6140
NIIN:01-371-0520
MSDS Number: CFKTT

Responsible Party
YUASA-EXIDE INC
645 PENN ST
READING, PA 19612-4205
US

Emergency Phone: 610-208-1975

Info Phone: 610-208-1975

Cage: IO592

Contractor
YUASA-EXIDE,INC.
READING, PA 19601 US

Telephone: 215-371-0400

Cage: 0W0V7

Ingredients

LEAD (SARA 313) (CERCLA)

CAS: 7439-92-1

RTECS: OF7525000

Fraction By Weight: 60%

OSHA PEL SEE 1910.1025

ACGIH TLV: 0.05MG/M3, A3; 9596

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


ANTIMONY (SARA 313) (CERCLA)

CAS: 7440-36-0

RTECS: CC4025000

Fraction By Weight: 2%

OSHA PEL 0.5 MG/M3

ACGIH TLV: 0.5 MG (SB)/M3; 9596

EPA Report Quantity: 5000 LBS

DOT Report Quantity: 5000 LBS


ARSENIC (SARA 313) (CERCLA)

CAS: 7440-38-2

RTECS: CG0525000

Fraction By Weight: 0.2%

OSHA PEL SEE 1910.1018

ACGIH TLV: 0.01 MG/M3, A1; 9596

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


CALCIUM, METAL

CAS: 7440-70-2

RTECS: EV8040000

Fraction By Weight: 0.2%


TIN

CAS: 7440-31-5

RTECS: XP7320000

Fraction By Weight: 0.2%

OSHA PEL 2 MG/M3

ACGIH TLV: 2 MG/M3; 9596


SULFURIC ACID (SARA 302/313) (CERCLA)/ELECTROLYTE

CAS: 7664-93-9

RTECS: WS5600000

Fraction By Weight: 10 - 30%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3/3 STEL; 9596

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


CASE MATERIAL (POLYPROPYLENE, POLYSTYRENE, STYRENE

Fraction By Weight: 5 - 10%


SILICONE DIOXIDE (GEL CELL BATTERIES ONLY)/SILICA,

CAS: 60676-86-0

RTECS: VV7328000

Fraction By Weight: 10%

OSHA PEL SEE TABLE Z-3

ACGIH TLV: 0.1 MG/M3 RDUST;9596


SHEET MOLDING COMPOUND (GLASS-REINFORCED POLYESTER)

Fraction By Weight: 10%

Hazards

LD50 LC50 Mixture:LD50 (ORAL, RAT) IS NOT RELEVANT.
Routes of Entry: Inhalation:NO Skin:NO Ingestion:YES
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:YES
Health Hazards Acute and Chronic:TARGET ORGANS:EYE, SKIN, CNS, LUNG, GI
TRACT. ACUTE- LEAD MAY CAUSE GI UPSET & FATIGUE. ACID MAY CAUSE
EYE, SKIN, MOUTH, THROAT, STOMACH & RESPIRATORY TRACT IRRITATION,
BURNS, CORNEAL & LUNG DAMAGE. C HRONIC- LEAD MAY CAUSE ANEMIA,
KIDNEY &NERVOUS SYSTEM DAMAGE. ACID CAN CAUSE BRONCHITIS, EROSION
OF TOOTH ENAMEL.
Explanation of Carcinogenicity:CONTAINS ARSENIC WHICH IS LISTED BY NTP
AND IARC AND REGULATED BY OSHA AS A CARCINOGEN. ALSO CONTAINS LEAD.
Effects of Overexposure:GI UPSET, LOSS OF APPETITE, DIARRHEA,
CONSTIPATION, CRAMPING, LACK OF SLEEP, FATIGUE, SEVERE IRRITATION,
BURNS, CORNEAL AND LUNG DAMAGE, BLINDNESS, IRRITABILITY, ULCERATION
Medical Cond Aggravated by Exposure:LEAD AND ITS COMPOUNDS CAN
AGGRAVATE CHRONIC FORMS OF KIDNEY, LIVER AND NEUROLOGIC DISEASES.
CONTACT OF SULFURIC ACID WITH SKIN MAY AGGRAVATE DISEASES SUCH AS
ECZEMA. ACID MIST AGGRAVATES LUNG DISEASE

First Aid

First Aid:OBTAIN MEDICAL ATTENTION IMMEDIATELY IN ALL CASES OF
EXPOSURE. EYES/SKIN:IMMEDIATELY FLUSH WITH WATER FOR 15 MINUTES.
KEEP EYELIDS OPEN. INHALATION:MOVE TO FRESH AIR. INGESTION:DO NOT
INDUCE VOMITING. IF CONSCIOUS, DRINK LARGE AMOUNT OF WATER.

Fire Fighting

Flash Point:NON-FLAMMABLE
Lower Limits:4.1% (H2)
Upper Limits:74.2% (H2)
Extinguishing Media:USE CARBON DIOXIDE, SAND, HALON/DRY CHEMICAL. WATER
APPLIED TO ELECTROLYTE GENERATES HEAT AND CAUSES IT TO SPATTER.
Fire Fighting Procedures:WEAR ACID-RESISTANT CLOTHING AND
NIOSH-APPROVED SELF-CONTAINED BREATHING APPARATUS WITH FULL
FACEPIECE OPERATED IN THE POSITIVE PRESSURE MODE.
Unusual Fire/Explosion Hazard:BATTERY CELLS MAY RUPTURE WHEN EXPOSED TO
EXCESSIVE HEAT. THIS COULD RESULT IN RELEASE OF CORROSIVE
MATERIALS. HYDROGEN GAS, IF PRESENT, IS EXPLOSIVE/FLAMMABLE.

Accidental Release

Spill Release Procedures:WEAR PROTECTIVE EQUIPMENTS. REMOVE
COMBUSTIBLES & IGNITION SOURCES (H2 MAY BE PRESENT). CONTAIN BY
DIKING AND COVER SPILL WITH SODA ASH OR QUICKLIME. MIX WELL. CHECK
THAT MIXTURE IS NEUTRAL. COLLECT A ND PLACE IN A DRUM. DO NOT FLUSH
TO SEWER.
Neutralizing Agent:SODA ASH (SODIUM CARBONATE), QUICKLIME (CALCIUM
OXIDE)

Handling

Handling and Storage Precautions:STORE NEAR EYEWASH FOUNTAIN AND SAFETY
SHOWER. STORAGE AREA SHOULD BE EQUIPPED WITH A DRAIN WHICH CAPTURES
SPILLS OF ACID FOR PROPER DISPOSAL.
Other Precautions:KEEP TERMINALS COVERED. AVOID SHORTING BATTERIES.
KEEP LIGHTED CIGARETTES, SPARKS, AND FLAMES AWAY FROM CHARGING
BATTERIES. KEEP OUT OF REACH OF CHILDREN. STORE AWAY FROM
INCOMPATIBLE MATERIALS. STORE IN AREA WITH ADEQUATE WATER SUPPLY.

Exposure Controls

Respiratory Protection:NOT REQUIRED UNDER NORMAL USE. USE
NIOSH-APPROVED ACID-MIST FILTER RESPIRATOR IF 1 MG/M3 TWA IS
EXCEEDED (ACID).
Ventilation:ADEQUATE GENERAL VENTILATION. IF MECHANICAL VENTILATION IS
USED, COMPONENTS MUST BE ACID-RESISTANT.
Protective Gloves:RUBBER OR PLASTIC
Eye Protection:SPLASH-PROOF CHEMICAL GOGGLES/FACESHIELD
Other Protective Equipment:RUBBER APRON AND BOOTS. EYES WASH STATION
AND SAFETY SHOWER. USE ACID-PROOF CLOTHING FOR MAJOR SPILLS.
Work Hygienic Practices:OBSERVE GOOD INDUSTRIAL HYGIENE PRACTICES AND
RECOMMENDED PROCEDURES. WASH AFTER HANDLING AND BEFORE EATING OR
DRINKING.
Supplemental Safety and Health

Chemical Properties

HCC:C1
NRC/State Lic Num:NOT RELEVANT
Spec Gravity:1.215-1.35 ACID
Viscosity:NOT RELEVANT
Evaporation Rate & Reference:NOT RELEVANT
Solubility in Water:NOT RELEVENT
Appearance and Odor:SEALED, BATTERY CONTAINING SULFURIC ACID AND LEAD.

Stability

Stability Indicator/Materials to Avoid:YES
SOLVENTS THAT DISSOLVE BATTERY CASE MATERIAL, ORGANIC MATERIALS, STRONG
REDUCING AGENTS, METALS, WATER, STRONG OXIDIZERS
Stability Condition to Avoid:HIGH HEAT, OPEN FLAMES, OVERCHARGING,
SMOKING, SPARKS
Hazardous Decomposition Products:LEAD OXIDE, HYDROGEN, SULFUR DIOXIDE,
SULFUR TRIOXIDE, CARBON MONOXIDE, METAL FUME, VAPOR OR DUST, TOXIC
ARSINE GAS

Disposal

Waste Disposal Methods:DISPOSE AS HAZARDOUS WASTE. OBSERVE ALL FEDERAL,
STATE AND LOCAL ENVIRONMENTAL REGULATIONS FOR ACID OR LEAD SCRAP.
SEND BATTERIES TO LEAD SMELTER FOR RECLAMATION FOLLOWING APPLICABLE
FEDERAL, STATE AN D LOCAL REGULATIONS.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.